Description
Our capacitor banks with detuned filters have been designed for power compensation purposes in networks with fluctuating load levels, a high content of harmonics and where there is a risk of resonance. Power variations are relatively slow (in seconds) so that the switching operations are carried out with contactors.
Applications
Its application is mainly focused on the compensation of installations with different loads, which require a regulated compensation, as a result of the power factor variations and where there is a high content of harmonics in the network.
- Fixed detuned filters. For the compensation of transformers and motors
- Automatic detuned filters, For the monitoring of variable loads
Technical features
Electrical features Operating voltage 400 V (50 Hz), 230/480 V (60 Hz)
(for other voltages, please ask)
Support voltage 440 V (400 V)
Capacity tolerance ± 10%
Unit composed of capacitor (460 V) Others upon request
Contactors with pre-insertion block and quick discharge resistor
Individual protection of each step with fuses with high
rupture power (HRP). NH-00 Series.
Two-pole protection circuit-breaker for capacitor bank and regulator operations.
Power factor regulator.
Detuned filters tuned at 189 Hz (50 Hz) /227 Hz (60 Hz) Others upon request for the protection against harmonics present in the network and to avoid the problems of resonance with fifth or higher order harmonics. Built-in thermostat for the disconnection of the step in case of excessive temperatures (90 ºC).
Auto-transformer
Add-ons Manual capacitor bank header switch
Automatic capacitor bank header switch
Automatic switch + Earth leakage protection at the capacitor bank’s header
Forced ventilation unit + thermostat
Polycarbonate plate to protect against direct contacts
Insulation level 3 / 15 kV
Discharge resistance 75 V / 3 minutes
Overload 1.3 times the rated current permanently
Overvoltage 10 % 8 over 24 hours
15 % up to 15 minutes over 24 hours
20 % up to 5 minutes over 24 hours
30 % up to 1 minutes over 24 hours
Auxiliary Voltage 230 V
Ambient conditions Class D temperature Daily mean: +45 ºC
Humidity 80% HR
Altitude 2 000 m
Construction features Protection Degree IP 31 Others upon request
Colour RAL 7035 Grey Others upon request
Annual mean: +35 ºC
Maximum: +50 ºC
Minimum: -25 ºC
Assembly conditions Type of assembly Vertical
Ventilation Natural or forced,
depending on the option Distance between capacitors Minimum, 2 cm
Standards IEC 60831-1, UNE 60831-1, IEC 61921, IEC 60439, IEC 61439